Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
4.6.4.1
Introduction
Generic parameters and diagnostic codes of PLCopen Safety POUs are presented below.
Table 16: General input parameters
Name
Type
Activate
BOOL
S_StartReset
BOOL
192
NOTICE!
The referenced standards in the following sub-chapters are used for information
only:
EN 954-1:1996
IEC 60204-1 Ed. 5.0:2003
IEC 61496-1:2004
IEC 62046/Ed.1:2005
ISO 12100-2:2003
MRL 98/37/EC, Annex I
EN 418:1992
EN 574:1996
EN 1088:1995
EN 953:1997
Use for functional safety certification the newest functional safety standards
Ä Chapter 1.8 "Applicable standards" on page 11.
Description
Variable or constant.
Activation of the FB. Initial value is FALSE.
This parameter can be connected to the variable, which represents the
status (active or not active) of the relevant safety device. This ensures no
irrelevant diagnostic information is generated if a device is disabled.
If FALSE, all output variables are set to the initial values.
If no device is connected, a static TRUE signal must be assigned.
Variable or constant.
FALSE (= initial value): Manual reset when PES is started (warm or cold).
TRUE: Automatic reset when PES is started (warm or cold).
This function shall only be activated if it is ensured that no hazard can occur
at the start of the PES. Therefore the use of the automatic circuit reset fea-
ture of the function blocks requires implementation of other system or appli-
cation measures to ensure that unexpected (or unintended) start-up does
not occur.
3ADR025091M0208, 12, en_US