Name
Data type
S_MutingLamp
BOOL
MutingEnable
BOOL
S_StartReset
BOOL
Reset
BOOL
DiscTimeEntry
TIME
MaxMutingTime
TIME
VAR_OUTPUT
Ready
BOOL
S_AOPD_Out
BOOL
S_MutingActive
BOOL
Error
BOOL
DiagCode
WORD
Note: Line control of muting sensor signals must be active in the safety loop.
2020/06/19
Initial value
Description, parameter values
FALSE
Variable or constant.
Indicates operation of the muting lamp.
FALSE: Muting lamp failure.
TRUE: No muting lamp failure.
FALSE
Variable or constant.
Command by the control system that enables the
start of the muting function when needed by the
machine cycle. After the start of the muting function,
this signal can be switched off.
FALSE: Muting not enabled
TRUE: Start of Muting function enabled
FALSE
Ä Table 16 "General input parameters" on page 192
Ä Table 16 "General input parameters" on page 192
FALSE
T#0s
Constant 0..4 s;
Max. discrepancy time for S_MutingSwitch11 and
S_MutingSwitch12 entering muting gate
T#0s
Constant 0..10 min;
Maximum time for complete muting sequence, timer
started when first muting sensor is actuated.
FALSE
Ä Table 17 "General output parameters"
on page 193
FALSE
Safety related output, indicates status of the muted
guard.
FALSE: AOPD protection field interrupted and muting
not active.
TRUE: AOPD protection field not interrupted or
muting active.
FALSE
Indicates status of Muting process.
FALSE: Muting not active.
TRUE: Muting active.
Ä Table 17 "General output parameters"
FALSE
on page 193
Ä Table 17 "General output parameters"
16#0000
on page 193
3ADR025091M0208, 12, en_US
Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
267