ABB AC500-S Safety User Manual page 369

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Error
Compo-
Device
severity
nent or
interface
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
9
1 ... 4
E2
9
1 ... 4
E2
9
1 ... 4
E3
1 ... 4
255
E3
1 ... 4
255
2020/06/19
Module
Channel
Error
30
2
10
30
2
13
30
2
17
30
2
18
30
2
19
30
2
25
30
2
37
30
2
38
30
2
42
30
2
43
30
2
52
30
2
54
30
3
30
1
0
17
1
0
43
31
0
43
30
1
26
30
1
27
3ADR025091M0208, 12, en_US
Usage of safety CPU with V2 non-safety CPU PM5xx
Error text
Remedy
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
Flash write error Restart safety PLC. If this
error persists, replace safety
PLC. Contact ABB technical
support.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
Checksum error
Restart safety PLC. If this
has occurred in
error persists, replace safety
safety PLC.
PLC.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
Cycle time error
Check safety PLC watchdog
in safety PLC
time.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
Internal error
Contact ABB technical sup-
port. Replace safety PLC.
PROFIsafe con-
Check F-Parameter configu-
figuration error
ration of I/O module and
reload boot project.
Access test
Check safety PLC switch
failed
address setting. Restart
safety PLC. If this error per-
sists, replace safety PLC.
Internal error
Check safety PLC switch
address setting. Restart
safety PLC. If this error per-
sists, replace safety PLC
Internal error
Replace module
Error in configu-
Create new configuration data
ration data,
safety PLC
cannot read
configuration
data
Error in configu-
Create boot project
ration data,
safety PLC
cannot read
configuration
data
369