ABB AC500-S Safety User Manual page 279

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Name
Data type
S_Acknowledge
BOOL
Reset
BOOL
MonitoringTime
TIME
VAR_OUTPUT
Ready
BOOL
S_SafetyActive
BOOL
S_SafetyRequest
BOOL
Error
BOOL
DiagCode
WORD
Typical timing
diagram
Fig. 112: Timing diagram for SF_SafetyRequest
The FB detects whether the actuator does not enter the safe state within the monitoring time.
The FB detects whether the acknowledge signal is lost while the request is still active.
2020/06/19
Initial value
Description, parameter values
FALSE
Variable.
Confirmation of the generic actuator, if actuator is in
the Safe state.
FALSE: Operation mode (non-safe).
TRUE: Safe mode.
FALSE
Ä Table 16 "General input parameters" on page 192
T#0s
Constant.
Monitoring of the response time between the safety
function request (S_OpMode set to FALSE) and the
actuator acknowledgment (S_Acknowledge switches
to TRUE).
Ä Table 17 "General output parameters"
FALSE
on page 193
FALSE
Confirmation of the safe state.
FALSE: Non-safe state.
TRUE: Safe state.
FALSE
Request to place the actuator in a safe state.
FALSE: Safe state is requested.
TRUE: Non-safe state.
FALSE
Ä Table 17 "General output parameters"
on page 193
Ä Table 17 "General output parameters"
16#0000
on page 193
3ADR025091M0208, 12, en_US
Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
279