ABB AC500-S Safety User Manual page 263

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

DiagCode
8012
8014
8314
8021
8122
8422
2020/06/19
State name
State description and output setting
Muting For-
Muting forward sequence is active either:
ward Active
- After rising trigger of the second entry MutingSwitch 12 or 11
1
has been detected.
- When both MutingSwitch 11 and 12 have been actuated in the
same cycle.
Monitoring of DiscTime11_12 is stopped. Monitoring of
MaxMutingTime is activated, when transition came directly from
state 8000.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
Muting For-
Muting forward sequence is active. MutingSwitch21 is the first
ward Step 1
actuated exit switch. Monitoring of DiscTime21_22 is started.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
Muting For-
Muting forward sequence is active. MutingSwitch22 is the first
ward Step 2
actuated exit switch. Monitoring of DiscTime21_22 is started.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
Muting For-
Muting forward sequence is still active. Both MutingSwitch21 and
ward Active
22 are actuated, the monitoring of DiscTime21_22 is stopped.
2
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
Muting Back-
Muting backward sequence is in starting phase after rising trigger
ward Start 1
of MutingSwitch21. Monitoring of DiscTime21_22 is activated.
Monitoring of MaxMutingTime is activated.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
Muting Back-
Muting backward sequence is in starting phase after rising trigger
ward Start 2
of MutingSwitch22. Monitoring of DiscTime21_22 is activated.
Monitoring of MaxMutingTime is activated.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
3ADR025091M0208, 12, en_US
Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
263