ABB AC500-S Safety User Manual page 293

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

DiagCode
C070
C080
C090
C111
Table 71: FB-specific status codes (no error):
DiagCode
0000
8001
8010
8000
2020/06/19
State name
State description and output setting
EDM Error
The signal at EDM1 is not valid in the actuator switching state.
31
In state 8000, the EDM1 signal is TRUE and the monitoring time
has elapsed.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
EDM Error
The signal at EDM2 is not valid in the actuator switching state.
32
In state 8000, the EDM2 signal is TRUE and the monitoring time
has elapsed.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
EDM Error
The signals at EDM1 and EDM2 are not valid in the actuator
33
switching state. In state 8000, the EDM1 and EDM2 signals are
TRUE and the monitoring time has elapsed.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Init Error
Similar signals at S_OutControl and Reset (R_TRIG at same
cycle) detected (may be a programming error).
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
State name
State description and output setting
Idle
The function block is not active (initial state).
Ready = FALSE
S_EDM_Out = FALSE
Error = FALSE
Init
Block activation startup inhibit is active. Reset required.
Ready = TRUE
S_EDM_Out = FALSE
Error = FALSE
Output Dis-
EDM control is not active. Timer starts when state is entered.
able
Ready = TRUE
S_EDM_Out = FALSE
Error = FALSE
Output
EDM control is active. Timer starts when state is entered.
Enable
Ready = TRUE
S_EDM_Out = TRUE
Error = FALSE
3ADR025091M0208, 12, en_US
Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
293