Fig. 44: Example of single channels with DX581-S

3.4.4 Internal data exchange

Inputs (bytes)
Outputs (bytes)

3.4.5 I/O configuration

The safety digital input/output module DX581-S does not store configuration data itself. The
configuration data is stored on the safety and non-safety CPUs.

3.4.6 Parameterization

The arrangement of the parameter data is performed by your system configuration software
Automation Builder. ABB GSDML file for PROFINET devices can be used to configure DX581-S
parameters in 3
The parameter setting directly influences the functionality of modules and reachable SIL
(IEC 61508), SILCL (IEC 62061) and PL (ISO 13849-1).
No.
Name
1
Check supply
Inputs
2
Input channel configu-
ration
3
Test pulse
4
Input delay
5
Discrepancy time*
Outputs
2020/06/19
Ix
UP
rd
party PROFINET F-Host systems.
Values
"On", "Off"
"Not used", "1 channel", "2 channel equivalent", "2
channel antivalent"
"Disabled", "Enabled"
"1 ms", "2 ms", "5 ms", "10 ms", "15 ms", "30 ms",
"50 ms", "100 ms", "200 ms", "500 ms"
"10 ms", "20 ms", "30 ms", "40 ms", "50 ms", "60 ms",
"70 ms", "80 ms", "90 ms", "100 ms", "150 ms",
"200 ms", "250 ms", "300 ms", "400 ms", "500 ms",
"750 ms", "1 s", "2 s", "3 s", "4 s", "5 s", "10 s", "20 s",
"30 s"
3ADR025091M0208, 12, en_US
DX581-S safety digital input/output module > Parameterization
ZP
Ox
UP
ZP
5
3
AC500-S safety modules
ZP
Default
"On"
"Not used"
"Disabled"
"5 ms"
"50 ms"
95