Function block-
Table 70: FB-specific error codes
specific error
DiagCode
and status
codes
C001
C011
C021
C031
C041
C051
C061
C071
2020/06/19
State name
State description and output setting
Reset Error
Static Reset signal in state 8001.
1
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Reset Error
Static Reset signal or same signals at EDM1 and Reset (rising
21
trigger at Reset and EDM1 at the same time) in state C010.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Reset Error
Static Reset signal or same signals at EDM2 and Reset (rising
22
trigger at Reset and EDM2 at the same time) in state C020.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Reset Error
Static Reset signal or same signals at EDM1, EDM2, and Reset
23
(rising trigger at Reset, EDM1, and EDM2 at the same time) in
state C030.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Reset Error
Static Reset signal or same signals at EDM1 and Reset (rising
31
trigger at Reset and EDM1 at the same time) in state C040.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Reset Error
Static Reset signal or same signals at EDM2 and Reset (rising
32
trigger at Reset and EDM2 at the same time) in state C050.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Reset Error
Static Reset signal or same signals at EDM1, EDM2, and Reset
33
(rising trigger at Reset, EDM1, and EDM2 at the same time) in
state C060.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Reset Error
Static Reset signal in state C070.
41
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
3ADR025091M0208, 12, en_US