Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Fig. 88: Typical timing diagram for SF_Equivalent
The function block monitors the discrepancy time between channel A and B, when switching to
TRUE and also when switching to FALSE.
Error behavior
S_EquivalentOut is set to FALSE. Error is set to TRUE. DiagCode indicates the error states.
There is no reset defined as an input is coupled with the reset of an error. If an error occurs in
the inputs, a new set of inputs with correct S_EquivalentOut must be able to reset the error flag.
(Example: if a switch is faulty and replaced, using the switch again results in a correct output.)