AC500-S safety modules
Safety CPU - SM560-S / SM560-S-FD-1 / SM560-S-FD-4 > Technical data
Memory
Data
User program memory of SM560-S
User program memory of SM560-S-FD-1 and
SM560-S-FD-4
User data memory (thereof 120 kB saved)
Performance
Data
Cycle time - binary
Cycle time - word
Cycle time - floating-point
Voltages,
Data
according to EN
Process and supply voltage (without ripple)
61131-2
Absolute limits (including ripple)
Ripple
Protection against reverse polarity
Allowed inter-
Data
ruptions of
DC supply interruptions
power supply,
according to EN
Time between 2 DC supply interruptions, PS2
61131-2
Environmental
Data
conditions
Operating temperature*
Storage temperature
Transport temperature
Humidity without condensation
Operating air pressure
Storage air pressure
Operating altitude
48
NOTICE!
Safety CPU -XC version is available for usage in extreme environmental condi-
Ä Appendix A "System data for AC500-S-XC" on page 360.
tions
DANGER!
Exceeding the permitted process or supply voltage range (< -35 V DC or >
+35 V DC) could lead to unrecoverable damage of the system.
3ADR025091M0208, 12, en_US
Value Unit
1 MB
1.3 MB
1 MB
Value Unit
0.05 µs/instruction
0.06 µs/instruction
0.50 µs/instruction
Value Unit
24 (-15 %, +20 %) V DC
19.2 ... 30 V DC
< 5 %
10 s
Value Unit
< 10 ms
> 1 s
Value Unit
0 ... +60 °C
-40 ... +85 °C
-40 ... +85 °C
max. 95 %
> 800 hPa
> 660 hPa
< 2000 m above sea
level