ABB AC500-S Safety User Manual page 270

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
DiagCode
C003
CYx4
C005
C006
C007
270
State name
State description and output setting
Error Muting
Error detected in muting lamp.
Lamp
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Error Muting
Error detected in muting sequence state 8000, 8011, 8311.
sequence
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Y = Status in the sequence
C0x4 = Error occurred in state 8000
C1x4 = Error occurred in state 8011
C2x4 = Error occurred in state 8311
CFx4 = Muting enable missing
x = Status of the sensors when error occurred (4 bits: LSB =
MS_11; next to LSB = MS_12).
Parameter
DiscTimeEntry or MaxMutingTime value out of range.
Error
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Error timer
Timing error: Active muting time (when S_MutingActive = TRUE)
MaxMuting
exceeds MaxMutingTime.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Error timer
Timing error: Discrepancy time for switching S_MutingSwitch11
Entry
and S_MutingSwitch12 from FALSE to TRUE > DiscTimeEntry.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
3ADR025091M0208, 12, en_US