Verification procedure for safe iParameter setting in AC500-S safety I/Os > Verification tables for iParameter settings in AC500-S safety I/Os
4.
Fig. 125: Compare "DX581-S" tab and "DX581-S Parameters" tab
1
"2 channel configuration 0/4" parameter in "DX581-
S" tab
2
"Inputs 0/4, discrepancy time" parameter in
"DX581-S Parameters" tab
5.
6.
7.
2020/06/19
Compare that "2 channel configuration 0/4" parameter in "DX581-S" tab have the same
value as "Inputs 0/4, discrepancy time" parameter in "DX581-S Parameters" tab.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verifica-
tion procedure and contact ABB technical support.
Repeat step 4 for the rest of input channel combinations:
Inputs 1/5, discrepancy time
Inputs 2/6, discrepancy time
Inputs 3/7, discrepancy time
Refer to "DX581-S" tab and calculate "Output channel 0" decimal equivalent (Dec_Out-
putChannel0) as:
Dec_OutputChannel0 = Detection_Value + Output_Value + 1
where
Detection_Value:
0 ➔ Off
64 ➔ On
Output_Value:
0 ➔ Not used
128 ➔ Used
Compare calculated Dec_OutputChannel0 with "Output 0, channel configuration".
They have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verifica-
tion procedure and contact ABB technical support.
Repeat step 6 for the rest of digital output channels (channel 1, channel 2, ... channel 7).
3ADR025091M0208, 12, en_US
Checklists for AC500-S commissioning
341