10.
2020/06/19
You can use PLC browser commands after login on safety CPU.
The following PLC browser commands (these commands can be called from CODESYS
Safety) are supported by the safety CPU:
?
- List of available browser commands
reflect
- Output of browser commands (for test purposes)
pid
- It shows the project ID
pinf
- It shows project information in AC500 format
getprgprop
- It shows program properties in AC500 format
getprgstat
- It shows program status in AC500 format
setpwd
- It sets safety CPU password (it is needed during login). This command is
active only if safety CPU "Enable debug" parameter was set to "ON" and
proper boot project was loaded to non-safety CPU.
delpwd
- It deletes safety CPU password. This command is active only if safety
CPU "Enable debug" parameter was set to "ON" and proper boot project
was loaded to non-safety CPU.
rtsinfo
- It shows firmware and boot project information in AC500 format
proddata
- It shows safety CPU production data in AC500 format
diagreset
- It resets diagnosis system of the safety CPU
diagack all
- It acknowledges all errors
diagack x
- It acknowledges all errors of class x (x= 1 .. 4)
diagshow
- It shows all errors in AC500 format
all
diagshow x - It shows all errors of class x
delappl
- It deletes boot project in the flash memory. This command is executed only
in DEBUG STOP state of the safety CPU. After safety CPU restart, one
shall check that no boot project is available in the safety CPU. This com-
mand is active only if safety CPU "Enable debug" parameter was set to
"ON" and proper boot project was loaded to non-safety CPU.
deluserdat: - It deletes user data in the flash memory. This command is executed only in
DEBUG STOP state of the safety CPU. It is executed immediately and is
active only if safety CPU "Enable debug" parameter was set to "ON" and
proper boot project was loaded to non-safety CPU.
applinfo
- It shows the application information, e.g., results of time profiling using
functions SF_APPL_MEASURE_BEGIN and SF_APPL_MEASURE_END.
applinfo
- It resets all application information, e.g., time measurement values.
reset
None of the above-mentioned safety CPU PLC browser commands changes the state
(e.g., from RUN to DEBUG RUN or DEBUG STOP, etc.) of the safety CPU.