Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Function block-
Table 55: FB-specific error codes
specific error
DiagCode
and status
codes
C001
C002
C003
CYx4
260
State name
State description and output setting
Reset Error
Static Reset condition detected after FB activation in state 8001.
1
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Reset Error
Static Reset condition detected in state 8003.
2
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Error Muting
Error detected in muting lamp.
Lamp
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Error Muting
Error detected in muting sequence state 8000, 8011, 8311, 8012,
sequence
8021, 8014, 8314, 8122, 8422, 8121, 8112, 8114 or 8414.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Y = Status in the sequence (6 states for forward and 6 states for
backward direction).
C0x4 = Error occurred in state 8000
C1x4 = Error occurred in state Forward 8011
C2x4 = Error occurred in state Forward 8311
C3x4 = Error occurred in state Forward 8012
C4x4 = Error occurred in state Forward 8014
C5x4 = Error occurred in state Forward 8314
C6x4 = Error occurred in state Forward 8021
C7x4 = Error occurred in state Backward 8122
C8x4 = Error occurred in state Backward 8422
C9x4 = Error occurred in state Backward 8121
CAx4 = Error occurred in state Backward 8114
CBx4 = Error occurred in state Backward 8414
CCx4 = Error occurred in state Backward 8112
...
CFx4 = Muting enable missing
x = Status of sensors when error occurred (4 bits: LSB = MS_11;
MS_12; MS_21; MSB = MS_22).