Checklists for AC500-S commissioning

Verification procedure for safe iParameter setting in AC500-S safety I/Os

No.
Item to check
9.
Ensure that average operating temperature for used
safety modules (AC500-S and AC500-S-XC) does not
exceed +40 °C (e.g., temperature sensors could be
placed in the control cabinet and connected to AI581-S
safety analog input channels for temperature monitoring).
10.
Verify that no automatic reboot of non-safety CPU is pro-
grammed in CODESYS non-safety program. The
automatic reboot of non-safety CPU would lead to
automatic restart of the safety CPU, which is directly
attached to non-safety CPU. Such automatic restart of
the safety CPU may not be accepted in some safety
applications.
Reviewer(s):
Machine/Application <ID>:
Signature:
Date:
6.5 Verification procedure for safe iParameter setting in AC500-S safety I/Os
This verification procedure has to be performed before commissioning of the final safety appli-
cation and relevant validation tests to confirm that F_iPar_CRC was calculated for a correct set
of iParameters.