After transition of S_OSSD_In to TRUE, the optional startup inhibit can be reset by a rising edge
at the Reset input.
After block activation, the optional startup inhibit can be reset by a rising edge at the Reset
input.
Function block-
Table 49: FB-specific error codes
specific error
DiagCode
and status
codes
C000
C001
C002
C003
C004
2020/06/19
State name
State description and output setting
Parameter
Invalid value at the TestTime parameter.
Error
Values between 0 ms and 150 ms are possible.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
Reset Error
Static Reset condition detected after FB activation.
1
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
Reset Error
Static Reset condition detected in state 8003.
2
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
Reset Error
Static Reset condition detected in state C010.
3
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
Reset Error
Static Reset condition detected in state C020.
4
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
3ADR025091M0208, 12, en_US