6.5.1 Verification procedure workflow

Personnel:
1.
2.
3.
4.
2020/06/19
Verification procedure for safe iParameter setting in AC500-S safety I/Os > Verification procedure workflow
Safety application engineer of AC500-S safety PLC
n
In Automation Builder, go to "Tools è Options...". Activate "Show generic device
configuration views" and instantiate a given type of safety I/O module (AI581-S, DI581-S
or DX581-S) in the Automation Builder tree (DX581-S is used as an example):
Go to the iParameter setting tab ( "DX581-S" , "DI581-S" or "AI581-S" ) for the given
module and set appropriate iParameter values (e.g., "Test Pulse" , "Input Delay" , etc.).
Verify against your safety application technical specification that all iParameters for all
safety I/O channels are set correctly.
Go to "F-Parameter" tab and press [Calculate] button. Copy calculated F_iPar_CRC value
from the "Checksum iParameter" field and paste it to "F_iPar_CRC" field of the F-Param-
eter editor.
3ADR025091M0208, 12, en_US