Severity
3
3
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
2020/06/19
Error code
Description
32775
Safety Module not found
32776
Safety Module has wrong
type
16640
Reserved switch address
setting.
16644
Boot project not loaded,
maximum power dip
reached
16648
Power dip data missed or
corrupted. Default power
dip data was flashed by
Safety PLC
16659
CRC error boot project
16909
Flash write error (produc-
tion data)
16935
More than one instance of
SF_WDOG_TIME_SET or
SF_MAX_POWER_DIP_S
ET
16922
No or wrong configuration
data from PM5x, run state
not possible
17421
Flash write error (boot
project)
17677
Flash write error (boot
code)
17933
Flash write error (firm-
ware)
18189
Flash write error (pass-
word)
18445
Flash write error (user
data)
18701
Flash write error (user
data)
18957
Flash write error (internal) Warning
19213
Flash write error (internal) Warning
19469
Flash write error (internal) Warning
32777
Program not started
because of configuration
error
32778
Program not started, no
application running in
Safety Module
3ADR025091M0208, 12, en_US
Usage of safety CPU with V3 non-safety CPU PM56xx
Remedy
Check configuration. At Safety
PLC: Check Safety PLC switch
address setting. Restart Safety
PLC. If this error persists,
replace Safety PLC.
Check configuration
Warning
Restart Safety PLC
Warning
Create new boot project and
restart Safety PLC
Warning
Warning
Create correct boot project at
PM5x
Warning
Warning
Warning
Warning
Warning
Warning
Check configuration
Check configuration, download
safety application to Safety
Module
387