AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Function block-
Table 67: FB-specific error codes
specific error
DiagCode
and status
codes
C001
C002
C010
C111
C211
Table 68: FB-specific status codes (no error):
DiagCode
0000
8001
8002
286
State name
State description and output setting
Reset Error
Static Reset signal in state 8001.
1
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
Reset Error
Static Reset signal in state 8003.
2
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
Control Error Static signal at ProcessControl in state 8010.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
Init Error
Simultaneous rising trigger at Reset and ProcessControl in state
8001.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
Lock Error
Simultaneous rising trigger at Reset and ProcessControl in state
8003.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
State name
State description and output setting
Idle
The function block is not active (initial state).
Ready = FALSE
S_OutControl = FALSE
Error = FALSE
Init
Block activation startup inhibit is active. Reset required.
Ready = TRUE
S_OutControl = FALSE
Error = FALSE
Safe
Triggered safety function.
Ready = TRUE
S_OutControl = FALSE
Error = FALSE