Value of STATE output on PROFIsafe F-Device stack
instance
PROFIsafe_STATE_FPAR_F_SRC_ADD_NOT_VALID
PROFIsafe_STATE_FPAR_WD_TIME_NULL
PROFIsafe_STATE_FPAR_F_SIL_ERR
PROFIsafe_STATE_FPAR_CRC_LENGTH
PROFIsafe_STATE_FPAR_VERSION_ERR
PROFIsafe_STATE_FPAR_CRC1_ERR
PROFIsafe_STATE_PARAM
PROFIsafe_STATE_DATAEX
PROFIsafe_STATE_DATAEX_F_OUTPUT_OK
PROFIsafe_STATE_
DATAEX_F_OUTPUT_OLD_CONSNR
PROFIsafe_STATE_
DATAEX_F_OUTPUT_PASSIVATED
2020/06/19
AC500-S libraries > SafetyDeviceExt_LV100_PROFIsafe_AC500_V27.lib
Meaning
Parameterization error: F-Source address is invalid or
overlapping with F-Source addresses of F-Host
instances.
Refer also to diagnosis
messages for SM560-S-FD-1 / SM560-S-FD-4 safety
CPUs " on page 371
Module 28, Error 2
Parameterization error: Watchdog time set to zero.
Refer also to diagnosis
messages for SM560-S-FD-1 / SM560-S-FD-4 safety
CPUs " on page 371
Module 28, Error 11
Parameterization error: Requested SIL is too high.
Refer also to diagnosis
messages for SM560-S-FD-1 / SM560-S-FD-4 safety
CPUs " on page 371
Module 28, Error 10
Parameterization error: Required CRC length does not
fit to the data length.
Refer also to diagnosis
messages for SM560-S-FD-1 / SM560-S-FD-4 safety
CPUs " on page 371
Module 28, Error 42
Parameterization error: PROFIsafe version error.
Refer also to diagnosis
messages for SM560-S-FD-1 / SM560-S-FD-4 safety
CPUs " on page 371
Module 28, Error 40
Parameterization error: CRC error in F-Parameters.
Refer also to diagnosis
messages for SM560-S-FD-1 / SM560-S-FD-4 safety
CPUs " on page 371
Module 28, Error 19
F-Host limitation error: F-Parameters accepted, but the
F-Device does not exchange data because of the
F-Host limitation.
No diagnosis message is available. If required, custom-
ized AC500 diagnosis message shall be generated.
F-Parameters are accepted, F-Device instance can
exchange process data.
The PROFIsafe output telegram for F-Host is valid.
The PROFIsafe output telegram for F-Host is valid with
an old consecutive number.
Communication error was detected or the F-Host sends
"activate_FV" in PROFIsafe control byte.
If required, customized AC500 diagnosis message shall
be generated from the application (if
PROFIsafe_STATE_
DATAEX_F_OUTPUT_PASSIVATED is detected on
STATE output of F-Device stack instance).
3ADR025091M0208, 12, en_US
Configuration and programming
Ä Table 105 "Specific error
Ä Table 105 "Specific error
Ä Table 105 "Specific error
Ä Table 105 "Specific error
Ä Table 105 "Specific error
Ä Table 105 "Specific error
297