B.2.2
Error messages for safety I/O modules
Table 107: Error messages for safety I/O modules (channel or module reintegration is possible)
Error
Compo-
Device
severity
nent or
interface
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
E3
14
1..10
2020/06/19
Module
Channel
Error
0
0..15
3
0
0..15
12
0
0..15
13
0
0..15
25
0
0..15
28
1
0..3
4
1
0..3
7
1
0..3
55
2
0..7
13
2
0..7
18
31
31
10
31
31
11
31
31
20
31
31
25
31
31
43
3ADR025091M0208, 12, en_US
Usage of safety CPU with V2 non-safety CPU PM5xx
Error text
Remedy
Discrepancy
Check discrepancy time
time expired
value, channel wiring and
sensor.
Test pulse error
Check wiring and sensor.
Channel test
Check wiring and sensor. If
pulse cross-talk
this error persists, replace I/O
error
module. Contact ABB tech-
nical support.
Channel stuck-
Check I/O module wiring.
at error
Restart I/O module, if needed.
If this error persists, replace
I/O module.
Channel cross-
Check I/O module wiring.
talk error
Restart I/O module, if needed.
If this error persists, replace
I/O module.
Measurement
Check channel wiring and
overflow at the
sensor power supply.
I/O module
Measurement
Check channel wiring and
underflow at the
sensor power supply.
I/O module
Channel value
Adjust tolerance window for
difference too
channels. Check channel
high
wiring and sensor configura-
tion.
Channel read-
Check I/O module wiring.
back error
Restart I/O module, if needed.
If this error persists, replace
I/O module.
Channel cross-
Check I/O module wiring.
talk error
Restart I/O module, if needed.
If this error persists, replace
I/O module.
Process voltage
Check process voltage
too high
Process voltage
Check process voltage
too low
PROFIsafe
Restart I/O module. If this
communication
error persists, contact ABB
error
technical support.
PROFIsafe
Restart I/O module. If this
watchdog timed
error persists, increase
out
PROFIsafe watchdog time.
Internal error in
Replace I/O module
the device
373