ABB AC500-S Safety User Manual page 364

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

System data for AC500-S-XC
A.3
Environmental tests
Storage
Humidity
Insulation test
Vibration resist-
ance
Shock resistance
EMC immunity
Electrostatic discharge (ESD)
Data
Electrostatic voltage in case of air discharge
Electrostatic voltage in case of contact discharge
Fast transient interference voltages (burst)
Data
Supply voltage units (DC)
Digital inputs/outputs (24 V DC)
Analog inputs/outputs
Communication lines, shielded
I/O supply (DC-out)
High energy transient interference voltages (surge) - common mode (CM)
Data
Supply voltage units (DC)
Digital inputs/outputs (24 V DC)
Analog inputs/outputs
Communication lines, shielded
I/O supply (DC-out)
High energy transient interference voltages (surge) - differential mode (DM)
Data
Supply voltage units (DC)
Digital inputs/outputs (24 V DC)
Analog inputs/outputs
I/O supply (DC-out)
Data
Influence of radiated disturbances: test field strength
Influence of line-conducted interferences: test voltage
364
IEC 60068-2-1 test Ab: cold withstand test -40 °C / 16 h
IEC 60068-2-2 test Bb: dry heat withstand test +85 °C / 16 h
IEC 60068-2-30 test Dd: Cyclic (12 h / 12 h) damp-heat test +55 °C, 93 %
relative humidity / +25 °C, 95 % relative humidity, 6 cycles
IEC 60068-2-78, stationary humidity test: +40 °C, 93 % relative humidity,
240 h
IEC 61131-2
IEC 61131-2 / IEC 60068-2-6: 5 Hz ... 500 Hz, 2 g (with SD memory card
inserted in non-safety CPU)
IEC 60068-2-64: 5 Hz ... 500 Hz, 4 g rms
IEC 60068-2-27: all 3 axes 15 g, 11 ms, half-sinusoidal
3ADR025091M0208, 12, en_US
Value Unit
8 kV
6 kV
Value Unit
4 kV
2 kV
2 kV
2 kV
2 kV
Value Unit
1 kV
1 kV
1 kV
1 kV
0.5 kV
Value Unit
0.5 kV
0.5 kV
0.5 kV
0.5 kV
Value Unit
10 V/m
10 V
2020/06/19