Name
Data type
S_SafeControl
BOOL
ProcessControl
BOOL
StaticControl
BOOL
S_StartReset
BOOL
S_AutoReset
BOOL
Reset
BOOL
VAR_OUTPUT
Ready
BOOL
S_OutControl
BOOL
Error
BOOL
DiagCode
WORD
2020/06/19
Initial value
Description, parameter values
FALSE
Variable.
Control signal of the preceding safety FB.
Typical function block signals from the library (e.g.,
SF_EStop, SF_GuardMonitoring, SF_TwoHandCon-
trolTypeII, and/or others).
FALSE: The preceding safety FBs are in safe state.
TRUE: The preceding safety FBs enable safety con-
trol.
FALSE
Variable or constant.
Control signal from the functional application.
FALSE: Request to set S_OutControl to FALSE.
TRUE: Request to set S_OutControl to TRUE.
FALSE
Constant.
Optional conditions for process control.
FALSE: Dynamic change at ProcessControl (FALSE
=> TRUE) required after block activation or triggered
safety function. Additional function start required.
TRUE: No dynamic change at ProcessControl
(FALSE => TRUE) required after block activation or
triggered safety function.
Ä Table 16 "General input parameters" on page 192
FALSE
Ä Table 16 "General input parameters" on page 192
FALSE
Ä Table 16 "General input parameters" on page 192
FALSE
FALSE
Ä Table 17 "General output parameters"
on page 193
FALSE
Controls connected actuators.
FALSE: Disable connected actuators.
TRUE: Enable connected actuators.
Ä Table 17 "General output parameters"
FALSE
on page 193
Ä Table 17 "General output parameters"
16#0000
on page 193
3ADR025091M0208, 12, en_US
Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
283