Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Function block-
Table 34: FB-specific error codes
specific error
DiagCode
and status
codes
C001
C002
Table 35: FB-specific status codes (no error):
DiagCode
0000
8001
8002
8003
8004
218
State name
State description and output setting
Reset Error
Reset is TRUE while waiting for S_ESPE_In = TRUE.
1
Ready = TRUE
S_ESPE_Out = FALSE
Error = TRUE
Reset Error
Reset is TRUE while waiting for S_ESPE_In = TRUE.
2
Ready = TRUE
S_ESPE_Out = FALSE
Error = TRUE
State name
State description and output setting
Idle
The function block is not active (initial state).
Ready = FALSE
S_ESPE_Out = FALSE
Error = FALSE
Init
Activation is TRUE. The function block was enabled. Check if
S_StartReset is required.
Ready = TRUE
S_ESPE_Out = FALSE
Error = FALSE
Wait for
Activation is TRUE. Check if Reset is FALSE and wait for
S_ESPE_In
S_ESPE_In = TRUE.
1
Ready = TRUE
S_ESPE_Out = FALSE
Error = FALSE
Wait for
Activation is TRUE. S_ESPE_In = TRUE. Wait for rising trigger of
Reset 1
Reset.
Ready = TRUE
S_ESPE_Out = FALSE
Error = FALSE
Wait for
Activation is TRUE. Safety demand detected. Check if Reset is
S_ESPE_In
FALSE and wait for S_ESPE_In = TRUE.
2
Ready = TRUE
S_ESPE_Out = FALSE
Error = FALSE
3ADR025091M0208, 12, en_US