Configuration and programming
AC500-S libraries > SafetyBase_PROFIsafe_LV200_AC500_V22.lib
This function block represents PROFIsafe F-Host instance to control and monitor the status of
the given F-Device (safety I/O, etc.)
Table 15: FB name: PROFISAFESTACK
Name
Data type
VAR_INPUT
activate_FV_C
BOOL
OA_C
BOOL
iPar_EN_C
BOOL
188
NOTICE!
Old versions
SafetyBase_PROFIsafe_AC500_V22_Ext.lib, version 1.0.1, library CRC:
f34d9a48
SafetyBase_PROFIsafe_AC500_V22.lib, version 1.0.0, library CRC:
7f64e267, license activation with PS501-S License Enabling Package
SafetyBase_PROFIsafe_AC500_V22.lib, version 1.0.0, library CRC:
c688eb23, special OEM version of PROFIsafe library
are NOT for use in new AC500-S customer projects.
NOTICE!
Loop-back check via bit 7 in status / control byte of PROFIsafe telegram is
implemented, which means that no further considerations against systematic
loop-back configuration errors shall be performed by end-users (refer to
www.profisafe.net for further details).
DANGER!
Not more than one communication error (CE_CRC or Host_CE_CRC output
signals become equal to TRUE) per 100 hours is allowed to be acknowledged
by the operator using OA_C input signal without consulting the responsible
safety personnel (refer to www.profisafe.net for further details).
Initial value
FALSE
FALSE
FALSE
3ADR025091M0208, 12, en_US
Ä [3].
Description, parameter values
Command (= TRUE) to activate fail-safe values in F-
Device or (= FALSE) for normal F-Device operation
Command (= TRUE) for operator acknowledgment
and resume of safety function by F-Device
This variable TRUE allows a safety control program
to switch the F-Device into a mode during which it
will accept iParameters. This mode is not supported
by AC500-S safety I/O modules (DI581-S, DX581-S,
AI581-S and SM560-S-FD-1 / SM560-S-FD-4)
2020/06/19