2.3 Safety loop

The safety loop, to which the AC500-S safety PLC belongs, consists of the following three parts:
sensors, safety PLC and actuators.
Fig. 2: Typical safety loop with AC500-S safety PLC
For the calculation of the PFH/PFD values of an exemplary safety system, a maximum of 15 %
is assumed for the safety PLC.

2.4 Safety values

Table 1: The following safety values shall be used for AC500-S safety modules:
Type
SIL
(1)
SILCL
SM560-S(-XC) /
3
SM560-S-FD-1(-
XC) / SM560- S-
FD-4(-XC)
AI581-S(-XC)
3
DI581-S(-XC)
3
Inputs of
3
DX581-S(-XC)
Outputs of
3
DX581-S(-XC)
with parameter
Detection =
"On"
Outputs of
2
DX581-S(-XC)
with parameter
Detection = "Off"
2020/06/19
Sensor
~35 % of safety loop PFH
PL
(3)
DC
(4)
MTTFd
(2)
e
97
1280
e
97
920
e
95
2270
e
94
2250
e
94
1985
d
85
200
3ADR025091M0208, 12, en_US
Safety loop
Safety PLC
Safety Input
Safety CPU
Module
Module
~1 5 % of safety loop PFH
(5)
PFHd
(6)
PFHd
1.90E-09
8.95E-11
2.95E-09
4.50E-10
1.45E-09
4.40E-10
1.45E-09
4.50E-10
1.60E-09
4.50E-10
1.19E-08
1.08E-08
Overview of AC500-S safety PLC
Safety Output
Actuator
Module
~50 % of safety loop PFH
(7)
PFDg
(8)
T1
(9)
7.90E-06
20
3.80E-05
20
3.70E-05
20
3.80E-05
20
3.80E-05
20
4.70E-04
20
Safety values
b
SFF
(10)
(11)
98
2
99
2
98
2
98
2
99
2
on
2
request
17