ABB AC500-S Safety User Manual page 242

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
DiagCode
8005
8006
8010
8020
242
State name
State description and output setting
ESPE Inter-
The automatic sensor test was faulty.
rupted
An external manual sensor test is necessary.
External Test
The support for the necessary external manual sensor test has
been activated at the FB (NoExternalTest = FALSE).
A TRUE signal at the sensor is required.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
End External
The automatic sensor test was faulty.
Test
An external manual sensor test is necessary.
The support for the necessary external manual sensor test has
been activated at the FB (NoExternalTest = FALSE).
The external manual test is complete.
The FB detected a complete sensor switching cycle (externally
controlled).
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
ESPE Free
The FB has not detected a safety demand.
No Test
The sensor has not been tested automatically.
Ready = TRUE
S_OSSD_Out = TRUE
S_TestOut = TRUE
TestPossible = TRUE
TestExecuted = FALSE
Error = FALSE
Test Request The automatic sensor test is active. Test Timer is started first
time.
The transmitter signal of the sensor is switched off by the FB.
The signal of the receiver must follow the signal of the transmitter.
Ready = TRUE
S_OSSD_Out = TRUE
S_TestOut = FALSE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
3ADR025091M0208, 12, en_US
2020/06/19