Configuration and programming
System configuration and programming > Checking of program and system configuration
4.
5.
How to verify
Each safety device has a separate section in the SVT checklist that begins with a heading with
the safety
the name of the safety device. The information in each safety device section depends on the
device sections
type of the safety device
1.
2.
3.
4.
5.
168
Verify that all of the safety devices in the Automation Builder project are listed in the SVT
checklist.
If a safety device is not in the list, use "Create Safety Configuration Data" from the
Automation Builder and run SVT again. Only configured and connected safety devices are
listed in the SVT because all disconnected devices are handled outside of the given
project.
ð After the line End of SVT checklist optional fields like date, signature, etc. are
included.
Continue to verify the contents of each safety device section.
Ä "Safety device sections" on page 161.
Verify that the automatic checks done by SVT for this safety device have passed.
ð If the automatic checks generate errors, you get an error message
automatic checks" on page 169:
Read the data checksum for the safety device.
Use this data checksum to verify changes to the data for this safety device. If the data
checksum is identical to a previously validated SVT checklist, the data for this safety
device is identical and you can skip the manual checks for it. If the data checksums are
not identical, repeat all of the manual checks for the safety device.
Verify the device type description. For 3
rd
For 3
party devices, verify that the version of the GSDML file shown in the SVT checklist
is identical to the expected version from the safety device vendor.
If applicable, verify that the position number of the safety device in the SVT checklist cor-
responds to its location in the safety project in Automation Builder. The position number
for the given safety device can change if their CM589-PNIO(-4) nodes are moved in the
project.
3ADR025091M0208, 12, en_US
rd
party devices only, also verify the Module ID.
Ä "Errors in the