Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Name
Data type
S_TwoHandOut
BOOL
Error
BOOL
DiagCode
WORD
Notes: No Reset input or Error output is required, because no test can be performed on both
switches.
Typical timing
diagram
Fig. 101: Timing diagram for SF_TwoHandControlTypeIII
After activation of the FB, any button set to TRUE is detected as an invalid input setting leading
to an error. The FB detects when the divergence of the input signals exceeds 500 ms.
Error behavior
In the event of an error, the S_TwoHandOut output is set to FALSE and remains in this safe
state.
The error state is exited when both buttons are released (set to FALSE).
228
Initial value
Description, parameter values
FALSE
Safety related output signal.
FALSE: No correct two hand operation.
TRUE: S_Button1 and S_Button2 inputs changed
from FALSE to TRUE within 500 ms and no error
occurred. The two hand operation has been per-
formed correctly.
Ä Table 17 "General output parameters"
FALSE
on page 193
Ä Table 17 "General output parameters"
16#0000
on page 193
3ADR025091M0208, 12, en_US
2020/06/19