Configuration and programming
System configuration and programming > Instantiation and configuration of safety modules / definition of variable names
Table 9: F-Parameters of AC500-S safety modules
F_Parameter
Definition
F_Check_SeqNr
This parameter defines whether
the consecutive number shall be
included in the CRC2. PROFIsafe
V2-mode
number has to be always included
in CRC2 generation.
Note:
F_Check_SeqNr is not shown in
the F-Parameter configuration for
SM560-S-FD-1 and
SM560-S-FD-4.
F_Check_iPar
Manufacturer-specific use within
homogeneous systems
F_SIL
Different safety functions using
safety-relevant communication
may require different safety integ-
rity levels. The F-Devices are able
to compare their own assigned SIL
with the configured SIL (F_SIL). If
it is higher than the SIL of the con-
nected F-Device, the "device
failure" status bit is set and a safe
state reaction is triggered
F_CRC_Length
Depending on the length of the
F I/O data (12 or 123 octets) and
the SIL level, a CRC of 2, 3, or 4
octets is required
F_Block_ID
Type identification of parameters
F_Par_Version
Version number of the F-Param-
eter set
136
Ä [3]: consecutive
Ä [3].
3ADR025091M0208, 12, en_US
Allowed values
"No Check" = 0
"Check" = 1
"No Check" = 0
"Check" = 1
"SIL1" = 0
"SIL2" = 1
"SIL3" = 2
"NoSIL" = 3
"3 octet CRC" = 0
"2 octet CRC" = 1
Not supported by SM560-
S:
"4 octet CRC" = 2
"No F_iPar_CRC within
F-Parameter block" = 0
"F_iPar_CRC within
F-Parameter block" = 1
"Valid for V1-mode" = 0
"Valid for V2-mode" = 1
Default value
"Check" = 1
"No Check" = 0
"SIL3" = 2
"3 octet CRC" = 0
(AC500-S safety I/O mod-
ules can work only with "3
octet CRC")
"F_iPar_CRC within
F-Parameter block" = 1 for
Safety I/Os
(AC500-S safety I/O mod-
ules can work only with
this default value)
"F_iPar_CRC within
F- Parameter block" = 0 for
SM560-S-FD-1 and
SM560-S-FD-4
"Valid for V2-mode" = 1
(AC500-S safety I/O mod-
ules can work only with
this default value)
2020/06/19