AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
DiagCode
8001
8002
8003
8005
8011
8311
262
State name
State description and output setting
Init
Function block has been activated.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
Safety
Safety demand detected by AOPD, muting not active.
Demand
Ready = TRUE
AOPD
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
Wait for
Safety demand or errors have been detected and are now
Reset
cleared. Operator acknowledgment by Reset required.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
Safe
Safety function activated.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
Muting For-
Muting forward sequence is in starting phase after rising trigger of
ward Start 1
MutingSwitch 11. Monitoring of DiscTime11_12 is activated. Moni-
toring of MaxMutingTime is activated.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
Muting For-
Muting forward sequence is in starting phase after rising trigger of
ward Start 2
MutingSwitch 12. Monitoring of DiscTime11_12 is activated. Moni-
toring of MaxMutingTime is activated.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
3ADR025091M0208, 12, en_US