Example for
1
SF_MutingSeq
in forward direc-
tion with four
sensors
If muting sensor MutingSwitch12 (MS_12) is activated by the product after MutingSwitch11
(MS_11), the muting mode is activated.
2
Muting mode remains active as long as MutingSwitch11 (MS_11) and MutingSwitch12 (MS_12)
are activated by the product. The product may pass through the light curtain without causing a
machine stop.
3
Before muting sensors MutingSwitch11 (MS_11) and MutingSwitch12 (MS_12) are disabled,
muting sensors MutingSwitch21 (MS_21) and MutingSwitch22 (MS_22) must be activated. This
ensures that muting mode remains active.
4
Muting mode is terminated if only muting sensor MutingSwitch22 (MS_22) is activated by the
product.
Muting condi-
Forward direction
tions
Muting condition 1 (to state 8011) (MS_11 is the first actuated entry switch). Start timer
MaxMutingTime:
MutingEnable AND (R_TRIG at MS_11 AND NOT MS_12 AND NOT MS_21 AND NOT MS_22)
Muting condition 2 (from state 8011 to state 8012) (MS_12 is the second actuated entry switch):
MutingEnable AND (MS_11 AND R_TRIG at MS_12 AND NOT MS_21 AND NOT MS_22)
Muting condition 3 (from state 8012 to state 8000) (MS_21 is the first released exit switch). Stop
timer MaxMutingTime:
2020/06/19
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Transmitter
MS_11 MS_12
MS_21 MS_22
Receiver
Transmitter
MS_11 MS_12
Receiver
Transmitter
MS_11 MS_12
MS_21 MS_22
Receiver
Transmitter
MS_11 MS_12
MS_21 MS_22
Receiver
3ADR025091M0208, 12, en_US
Configuration and programming
Danger
zone
Danger
zone
MS_21 MS_22
Danger
zone
Danger
zone
247