ABB AC500-S Safety User Manual page 355

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Information
about the used
function block
parameters
Function block
EStop_S1
OC_K1_K2
EDM_K1_K2
2020/06/19
Input
Constant value
S_StartReset
FALSE
S_AutoReset
FALSE
S_StartReset
TRUE
S_AutoReset
TRUE
StaticControl
FALSE
S_StartReset
FALSE
MonitoringTime
T#200ms
3ADR025091M0208, 12, en_US
Safety application examples
Example 3: two-hand control > Additional notes
Description
No automatic reset when PES is started
No automatic reset, user reset/acknowledge
necessary
Automatic reset allowed when PES is started
Automatic reset, no user reset/acknowledge
necessary
A dynamic change of the signal Appl_Control
(rising edge) is required after block activation
or a triggered safety function (S_SafeControl
= FALSE)
No automatic reset when PES is started
The maximum response time of both feed-
back signals S_EDM1 and S_EDM2 is moni-
tored to be within 200 ms.