Usage of safety CPU with V2 non-safety CPU PM5xx
Table 106: Mapping of AC500/AC500-S errors to PROFINET channel errors
AC500/AC500-S
error
28
1
2
11
10
42
40
19
372
PROFINET channel error
type
64
65
66
67
68
69
70
71
3ADR025091M0208, 12, en_US
PROFINET diagnostic information
Mismatch of safety destination address
(F_Dest_Add)
Safety destination address not valid
(F_Dest_Add)
Safety source address not valid
(F_Source_Add)
Safety watchdog time value is 0 ms
(F_WD_Time)
Parameter "F_SIL" exceeds SIL from spe-
cific device application
Parameter "F_CRC_Length" does not
match the generated values
Version of F-Parameter set incorrect
CRC1-Fault