ABB AC500-S Safety User Manual page 120

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

AC500-S safety modules
AI581-S safety analog input module > Technical data
Cable length
Data
Conductor cross section of analog cables
Max. analog cable length, shielded
Cooling
The natural convection cooling must not be hindered by cable ducts or other parts in the switch-
gear cabinet.
Allowed inter-
Data
ruptions of
DC supply interruptions
power supply,
according to EN
Time between 2 DC supply interruptions, PS2
61131-2
Environmental
Data
conditions
Operating temperature*
Storage temperature
Transport temperature
Humidity without condensation
Operating air pressure
Storage air pressure
Operating altitude
Storage altitude
* Extended temperature ranges (below 0 °C and above +60 °C) can be supported in special ver-
sions of AI581-S
Creepage dis-
The creepage distances and clearances meet the overvoltage category II, pollution degree 2.
tances and
clearances
Power supply
For the supply of modules, power supply units according to PELV/SELV specifications must be
units
used.
Electromagnetic
For information on electromagnetic compatibility refer to the latest TÜV SÜD Report
compatibility
Mechanical
Data
properties
Degree of protection
Housing
Vibration resistance acc. to EN 61131-2 (all three axes),
continuous 3.5 mm
Vibration resistance acc. to EN 61131-2 (all three axes),
continuous 1 g *
Shock test (all three axes), 11 ms half-sinusoidal
MTBF
* Higher values on request
120
Ä Appendix A "System data for AC500-S-XC" on page 360.
3ADR025091M0208, 12, en_US
Value Unit
> 0.14 mm²
100 m
Value Unit
< 10 ms
> 1 s
Value Unit
0 ... +60 °C
-40 ... +85 °C
-40 ... +85 °C
max. 95 %
> 800 hPa
> 660 hPa
< 2000 m above sea
level
< 3500 m above sea
level
Value Unit
IP 20
according to UL 94
2 ... 15 Hz
15 ...150 Hz
15 g
102 years
Ä [2].
2020/06/19

Advertisement

Table of Contents
loading

Table of Contents