ABB AC500-S Safety User Manual page 103

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Allowed inter-
Data
ruptions of
DC supply interruptions
power supply,
according to EN
Time between 2 DC supply interruptions, PS2
61131-2
Environmental
Data
conditions
Operating temperature*
Storage temperature
Transport temperature
Humidity without condensation
Operating air pressure
Storage air pressure
Operating altitude
Storage altitude
* Extended temperature ranges (below 0 °C and above +60 °C) can be supported in special ver-
sions of DX581-S
Creepage dis-
The creepage distances and clearances meet the overvoltage category II, pollution degree 2.
tances and
clearances
Power supply
For the supply of modules, power supply units according to PELV/SELV specifications must be
units
used.
Electromagnetic
For information on electromagnetic compatibility refer to the latest TÜV SÜD Report
compatibility
Mechanical
Data
properties
Degree of protection
Housing
Vibration resistance acc. to EN 61131-2 (all three axes),
continuous 3.5 mm
Vibration resistance acc. to EN 61131-2 (all three axes),
continuous 1 g *
Shock test (all three axes), 11 ms half-sinusoidal
MTBF
* Higher values on request
Self-test and
Start-up and runtime tests: Program flow control, RAM, CPU, cross-talk, stuck-at-1, etc.
diagnostic func-
tions
Dimensions,
Data
weight
W x H x D
Weight
2020/06/19
Ä Appendix A "System data for AC500-S-XC" on page 360.
3ADR025091M0208, 12, en_US
DX581-S safety digital input/output module > Technical data
0 ... +60 °C
-40 ... +85 °C
-40 ... +85 °C
max. 95 %
according to UL 94
15 ... 150 Hz
67.5 x 76 x 62 mm
AC500-S safety modules
Value Unit
< 10 ms
> 1 s
Value Unit
> 800 hPa
> 660 hPa
< 2000 m above sea
level
< 3500 m above sea
level
Ä [2].
Value Unit
IP 20
2 ... 15 Hz
15 g
73 years
Value Unit
~ 130 g
103

Advertisement

Table of Contents
loading

Table of Contents