Fig. 24: Example of single channel with DI581-S
3.3.4 Internal data exchange
Inputs (bytes)
Outputs (bytes)
3.3.5 I/O configuration
The safety digital input module DI581-S does not store configuration data itself. The configura-
tion data is stored on the safety and non-safety CPUs.
3.3.6 Parameterization
The arrangement of the parameter data is performed by your system configuration software
Automation Builder. ABB GSDML file for PROFINET devices can be used to configure DI581-S
parameters in 3
The parameter setting directly influences the functionality of modules and reachable SIL
(IEC 61508), SILCL (IEC 62061) and PL (ISO 13849-1).
No.
Name
1
Check supply
2
Configuration
3
Test pulse
4
Input delay
5
Discrepancy time*
* Available only for "2 channel equivalent" and "2 channel antivalent" configuration
3.3.7 Circuit examples
Examples of electrical connections and reachable SIL (IEC 61508), SILCL (IEC 62061) and PL
(ISO 13849-1) with DI581-S module are presented below.
2020/06/19
UP
rd
party PROFINET F-Host systems.
Values
"On", "Off"
"Not used", "1 channel", "2 channel equivalent", "2
channel antivalent"
"Disabled", "Enabled"
"1 ms", "2 ms", "5 ms", "10 ms", "15 ms", "30 ms",
"50 ms", "100 ms", "200 ms", "500 ms"
"10 ms", "20 ms", "30 ms", "40 ms", "50 ms", "60 ms",
"70 ms", "80 ms", "90 ms", "100 ms", "150 ms",
"200 ms", "250 ms", "300 ms", "400 ms", "500 ms",
"750 ms", "1 s", "2 s", "3 s", "4 s", "5 s", "10 s", "20 s",
"30 s"
3ADR025091M0208, 12, en_US
DI581-S safety digital input module > Circuit examples
Ix
ZP
6
2
AC500-S safety modules
Default
"On"
"Not used"
"Disabled"
"5 ms"
"50 ms"
69