ABB AC500-S Safety User Manual page 240

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Configuration and programming
AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
DiagCode
C005
C006
C007
C010
C020
240
State name
State description and output setting
Reset Error
Static Reset condition detected in state 8006.
5
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
Reset Error
Static Reset condition detected in state C000.
6
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
Reset Error
Static Reset condition detected in state 8013.
7
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = TRUE
Error = TRUE
Test Error 1
Test time elapsed in state 8020.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
Test Error 2
Test time elapsed in state 8030.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
3ADR025091M0208, 12, en_US