ABB AC500-S Safety User Manual page 54

Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

AC500-S safety modules
Generic safety I/O module behavior > Safety I/O module states
RUN (module
passivation):
alternating
blinking of
ERR1 and ERR2
LEDs
PROFIsafe communication is up and running. The safety application is running with a present
module error.
The module and, as a result, all its channels are passivated. Possible reasons for module passi-
vation are:
PROFIsafe communication failure (CRC error)
PROFIsafe watchdog timeout exceeded
Undervoltage/overvoltage detected (Device_Fault status bit = 1)
The fail-safe value "0" is transferred to the safety PLC for all passivated input channels, if the
connection to the PROFIsafe F-Host is possible. The safety application continuously attempts to
establish a communication to the safety CPU, if the communication is broken. All passivated
output channels have a state of "0".
A state transition to another RUN mode is only possible if the detected error is gone.
PROFIsafe status bits in the F-Host for safety I/O module (if communication is possible!):
OA_Req_S = 0
FV_activated_S = 1
Device_Fault = 1 (in case of undervoltage/overvoltage detected) and/or CE_CRC = 1 (in case of
communication error) and/or WD_timeout = 1 (in case of watchdog timeout)
Process data bits in the safety I/O module process image:
PROFIsafe diagnostic bit = 0
Channel process value = 0
Reintegration request bit = 0
54
1.0 I0-
PWR
2.0I0+
3.0 I2-
1.1 FE
3.1 FE
2.1
1.2 I1-
2.2I1+
3.2 I3-
1.3 FE
2.3
3.3 FE
1.4
2.4
3.4
ADDR
2.5
1.5
3.5
x10H
4
3
5
6
2
1.6
2.6
3.6
1
7
0
8
F
9
E
A
1.7
2.7
3.7
D
B
C
ADDR
1.8 UP
2.8UP
3.8 UP
x01H
4
3
5
2
6
1.9 ZP
2.9ZP
3.9 ZP
1
7
0
8
F
9
E
A
D
B
C
ERR1
UP 24VDC 2W
3ADR025091M0208, 12, en_US
AI581-S
4.0I2+
4.1
4.2I3+
4.3
4.4
4.5
4.6
4.7
4.8UP
4.9ZP
ERR2
4SAI
Safety Analog Input
2020/06/19

Advertisement

Table of Contents
loading

Table of Contents