AC500-S libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Table 29: FB-specific status codes (no error):
DiagCode
0000
8005
8000
8004
4.6.4.5
SF_EmergencyStop
Standards
Requirements
EN 418:1992
3. Definitions
4.1.12 ... Resetting the control device shall not by itself cause a restart command.
EN 954-1:1996
5.4 Manual reset
ISO 12100-2:2003
4.11.4 Restart following power failure/spontaneous restart
IEC 60204-1,
9.2.2. Stop Functions
Ed. 5.0:2003
210
State name
State description and output setting
Idle
The function block is not active (initial state).
Ready = FALSE
Error = FALSE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE
Mode-
State after activation or when S_ModeX has changed (unless
Changed
locked) or after reset of an error state.
Ready = TRUE
Error = FALSE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE
ModeSe-
Valid mode selection, but not yet locked.
lected
Ready = TRUE
Error = FALSE
S_AnyModeSel = TRUE
S_ModeXSel = Selected X is TRUE, others are FALSE.
ModeLocked Valid mode selection is locked.
Ready = TRUE
Error = FALSE
S_AnyModeSel = TRUE
S_ModeXSel = Selected X is TRUE, others are FALSE.
3ADR025091M0208, 12, en_US