Nur für den internen Gebrauch
Table 4-2
Electrical Connection Values (for U.S. only)
Nominal
Nominal voltage range
voltage
from
120 V AC/
110 V AC
60 Hz
WARNING
7
Never connect a HiPath 3800 system or a combination of HiPath 3800 systems di-
rectly to a wall socket. Use a UL-listed or CSA-certified surge protector for every two
cabinets.
AC Outlet Requirements
A UL-listed or CSA-certified surge protector must be connected between the socket and
the system. Two cabinets can be connected to each surge protector. Never connect a Hi-
Path 3800 system or a combination of systems directly to a wall socket.
The power source may not be more than 2.4 m (8 ft.) from the system.
The power source must provide 120 V AC (single-phase, fused) power at 50-60 Hz and 20
A.
A warning should be attached to the circuit breaker to prevent accidental removal of power.
An independent electric circuit with an isolated ground conductor should be used.
The system must be properly grounded before startup (see description in Section 4.1.3.4).
A31003-H3590-S100-7-7620, 06/2012
HiPath 3000/5000 V9, Service documentation
Nominal Frequency
to
from
130 V AC
47 Hz
Wall Outlet Configura-
Range
to
63 Hz
NEMA 5-15, 2-pin, 3-
wire, earth
inst_h3.fm
Installing HiPath 3000
Installing HiPath 3800
tions
4-5