UPSC-DR

Introduction
The UPSC-DR board (S30122-K7373-A900, S30122-K7373-M900 (Figure 3-26)) is used in Hi-
Path 3500 and HiPath 3300 (19-inch housing).
This module supports power supply and battery management functions. No other components
are required if it is operated as an AC power supply. To maintain short-term battery emergency
operation after a power failure, that is, to use uninterruptible power supply functions, you must
also connect a battery pack (see Section 9.1.3).
Warning
7
The UPSC-DR power supply unit is only released for permanent AC power supply.
Permanent operation at a direct-current system is not allowed.
A DC power supply unit is only connected to bridge an AC power failure (emergency
battery operation).
If a 48-V direct-current system is being used instead of a battery pack for DC power
supply, connection must be performed as for a battery pack. The 48-V direct-current
system must not exceed the limit of 60 V in operating mode, during loading, and
when an error occurs. The direct-current system must not be connected to the
UPSC-DR if this cannot be guaranteed!
Danger
7
The UPSC-DR board is not insulated.
Consequently, a system using a UPSC-DR may only be operated with a closed
housing.
Before opening the housing, make sure that the system is de-energized as follows:
by disconnecting the battery voltage and line voltage at any connected PB3000.
by disconnecting the line cord attached to any connected batteries (PB3000).
by disconnecting the line cord attached to any connected Powerbox PB3000.
by disconnecting the power plug.
If the power supplied by the UPSC-DR is insufficient, an external power supply
PB3000
with LUNA2) can be installed to provide additional power. To do this, connect the DC
port on the PB3000 to the special -48-Vdc input on the UPSC-DR. The UPSC-DR's internal -
48 V output is deactivated when the external power supply is connected. For emergency bat-
tery operation in the event of power failure, 4 x 12-V/7-Ah batteries (4 x V39113-W5123-E891)
must be installed in the Powerbox PB3000.
Licensed batteries for UPSC-DR
4 x V39113-W5123-E891 (4 x 12 V/7 Ah batteries)
These are the only batteries released for connection to UPSC-DR and installation in Powerbox
PB3000.
3-74
Nur für den internen Gebrauch
A31003-H3590-S100-7-7620, 06/2012
HiPath 3000/5000 V9, Service documentation
(Power box