This section contains information on how to install the HiPath 3800 communication system in
a 19-inch cabinet. This chapter describes the standard installation procedures for the basic sys-
tem. Refer to Chapter 9 for information about supplementary equipment or expansions.
4.1.4.1

Selecting the Installation Site

The installation site is generally determined by the 19-inch cabinet already installed.
The following specifications must be observed when selecting a location:
The 19-inch cabinets provided for installing the HiPath 3800 components must have the
following characteristics:
Components installed in the 19-inch cabinet must be accessible from both the front
and the rear.
It should be possible to install 19-inch components both at the front and at the rear (
four vertical bars).
It is recommended that the width of the cabinet measure 700 to 800 mm; the depth at
least 600 mm. Deeper cabinets (800 - 900 mm) make installation, cable servicing, and
the installation of additional components in the rear of the cabinet much easier.
The support brackets required for installing the system cabinets must have a minimum
ultimate load of 40 kg. The support brackets must be purchased from the relevant 19-
inch cabinet supplier.
The system cabinets must be fixed to the cabinet bars using the angle brackets includ-
ed in the delivery.
One height unit (one height unit is approx. 1.7" = 43 mm) must be kept clear above the cab-
inet to accommodate the gray plastic cover (Figure 4-9) attached to the top of the system
cabinets. Never remove this plastic cover.
The following minimum clearance must be provided in order to ensure adequate ventilation
of the system cabinets in the 19-inch cabinet (see Figure 4-10):
three height units between two stacked system cabinets.
one height unit above one system cabinet if a patch panel is being installed, for exam-
ple.
To guarantee sufficient heat dissipation, the basic cabinet must be mounted at the lowest
position in a 19-inch cabinet. In a 19-inch cabinet with active (heat-emitting) components
already installed, the lowest position must be cleared for installation of the basic cabinet.
If inactive components (e.g. patch panel) are involved, the basic cabinet can also be in-
stalled above them.