Plc Side Setting (Mp2000 Series, Mp920 Series) - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

Ethernet setting
Item
Description
The host is displayed. (The host is
Host
indicated with an asterisk (*).)
Set the network No. of the
N/W No.
connected Ethernet module.
(Default: blank)
Set the station No. of the
*2
connected Ethernet module.
PLC No.
(Default: blank)
Type
YASKAWA (fixed)
Set the IP address of the
*1
connected Ethernet module.
IP address
(Default: blank)
Set the port No. of the connected
Port No.
Ethernet module.
(Default: 10500)
Communication
Select a communication protocol.
format
(Default: UDP)
*1
Connection with the PLC is unavailable if the IP address is
the default value. Set the value to the IP address of the PLC
to be connected.
*2
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
 Communication detail settings
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GT
User's Manual
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
6.3.3
POINT
POINT
POINT
YASKAWA PLC
For details of YASKAWA PLCs, refer to the following
manuals.
Parameter settings
Make the parameter settings with a peripheral tool.
Set value
(1) Settings for 218IF-01
1 to 239
1 to 64
YASKAWA (fixed)
PLC side IP
address
256 to 65534
Parameter
UDP, TCP
setting
Local Port:
TCP/IP
Setting
6. CONNECTION TO YASKAWA PLC
PLC side setting (MP2000
series, MP920 series)
YASKAWA PLC user's Manual
Item
Set value
Local IP Address
[ ].[ ].[ ].[ ]
Response Time
Count of Retry
(Number of Retries)
*1
CNO
(Connection Number)
Local Port (Local
10500
Station's Port Number)
Node IP Address
(Remote Station's IP
[ ].[ ].[ ].[ ]
*2
Address)
Node Port (Remote
*2
Station's Port Number)
UDP
Connection Type
(recommended)
Extended
Protocol Type
MEMOBUS
Code
BIN
Node Name (Remote
GOT1000
Station's Name)
Subnet Mask
[ ].[ ].[ ].[ ]
Gateway IP Address
[ ].[ ].[ ].[ ]
System Port No.
(Diagnostic/
10000
Engineering Port No.)
TCP (Transmission
Control Protocol) Zero
3 sec
Window Timer Value
TCP Retry Time
500ms
TCP Close Time
60 sec
IP Assemble Time
30 sec
MAX. Packet Length
1500 bytes
*1
When MITSUBISHI PLC and YASKAWA PLC are used
together in the same network, do not set the same value for
the PLC No. of MITSUBISHI PLC and the CNO (Connection
number) of YASKAWA PLC.
*2
Set the same the Node IP Address (Remote Station's IP
Address) and the Node Port (Remote Station's Port Number)
as the Local IP Address and the Local Port (Local Station's
Port Number) on the GOT side.
For the Local IP Address and the Local Port (Local Station's
Port Number) on the GOT side, refer to the following.
6.3.2 ■ Ethernet setting
6.3 Ethernet Connection
Range
PLC side IP
address
Not required for
0
communication
with GOT
Not required for
0
communication
with GOT
1
1 to 20
256 to 65534
IP address
of GOT
Port No.
[ ]
of GOT
UDP/TCP
Extended
MEMOBUS,
MEMOBUS,
MELSEC,
None,
MODBUS/TCP
RTU, BIN, ACII
Name of GOT
PLC side
setting
6 - 23
1
2
3
4
5
6
7
8