Plc Side Setting (Mp2000 Series, Mp920 Series) - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal (non-mitsubishi electric products 2)
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

6.3.4

PLC side setting (MP2000 series, MP920 series)

■1. Parameter settings
Make the parameter settings with a peripheral tool.
(1) Settings for 218IF-01
Parameter setting
Local Port: TCP/IP
Setting
*1
*2
6 - 30
6.3 Ethernet Connection
POINT
POINT
POINT
YASKAWA PLC
For details of YASKAWA PLCs, refer to the following manuals.
YASKAWA PLC user's Manual
Item
Local IP Address
Response Time
Count of Retry (Number of Retries)
*1
CNO
(Connection Number)
Local Port (Local Station's Port Number)
Node IP Address (Remote Station's IP
*2
Address)
Node Port (Remote Station's Port Number)
Connection Type
Protocol Type
Code
Node Name (Remote Station's Name)
Subnet Mask
Gateway IP Address
System Port No. (Diagnostic/Engineering Port
No.)
TCP (Transmission
Control Protocol) Zero Window Timer Value
TCP Retry Time
TCP Close Time
IP Assemble Time
MAX. Packet Length
When MITSUBISHI ELECTRIC PLC and YASKAWA PLC are used together in the same network, do not set the same value for
the Station of MITSUBISHI ELECTRIC PLC and the CNO (Connection number) of YASKAWA PLC.
Set the same the Node IP Address (Remote Station's IP Address) and the Node Port (Remote Station's Port Number) as the
Local IP Address and the Local Port (Local Station's Port Number) on the GOT side.
For the Local IP Address and the Local Port (Local Station's Port Number) on the GOT side, refer to the following.
6.3.3 ■4. Connected Ethernet Controller Setting
Set value
[ ].[ ].[ ].[ ]
0
0
1
10500
[ ].[ ].[ ].[ ]
*2
[ ]
UDP (recommended)
Extended MEMOBUS
BIN
GOT2000
[ ].[ ].[ ].[ ]
[ ].[ ].[ ].[ ]
10000
3 sec
500ms
60 sec
30 sec
1500 bytes
Range
PLC side IP
address
Not required for
communication with GOT
Not required for
communication with GOT
1 to 20
256 to 65534
IP address
of GOT
Port No.
of GOT
UDP/TCP
Extended MEMOBUS,
MEMOBUS,
MELSEC,
None,
MODBUS/TCP
RTU, BIN, ACII
Name of GOT
PLC side
setting