Input Filter Time Constant (Pr. 74); Reset Selection/Disconnected Pu Detection/Pu Stop Selection (Pr. 75) - Mitsubishi Electric FR-E540-0.4K-EC Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-E540-0.4K-EC:
Table of Contents

Advertisement

z z

Input filter time constant (Pr. 74)

4.2.29 Input filter time constant (Pr. 74)
Pr. 74 "filter time constant"
You can set the input section's internal filter constant for an external voltage or current
frequency setting signal.
y Effective for eliminating noise in the frequency setting circuit.
y Increase the filter time constant if steady operation cannot be performed due to
noise. A larger setting results in slower response. (The time constant can be set
between approximately 1ms to 1s with the setting of 0 to 8. A larger setting results in
a larger filter time constant.)
Parameter
Factory
Number
Setting
74
4.2.30 Reset selection/disconnected PU detection/PU stop
selection (Pr. 75)
Pr. 75 "reset selection/disconnected PU detection/PU stop selection"
You can select the reset input acceptance, control panel (FR-PA02-
PU04) connector disconnection detection function and PU stop function.
y Reset selection
y PU disconnection detection : When it is detected that the control panel (FR-PA02-
y PU stop selection
Parameter
Factory
Number
Setting
75
Setting Range
1
0 to 8
: You can select the reset function input timing.
/PU (FR-PU04) is disconnected from the inverter for
more than 1 second, the inverter outputs an alarm
code (E.PUE) and comes to an alarm stop.
: When an alarm occurs in any operation mode, you can
stop the inverter from the PU by pressing the
Setting Range
14
0 to 3, 14 to 17
102
PARAMETERS
) or PU (FR-
02
)
02
STOP
key.
RESET
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents