Reset Selection / Disconnected Pu Detection / Pu Stop Selection - Mitsubishi Electric FR-E800 Instruction Manual

Advertisement

8.2
Reset selection / disconnected PU detection / PU
stop selection
The reset input acceptance, disconnected PU connector detection function, and PU stop function can be selected.
Pr.
Name
Reset selection/
disconnected PU
75
detection/PU stop
selection
E100
Reset selection
Disconnected PU
E101
detection
E102
PU stop selection
E107
Reset limit
The parameters above do not return to their initial values even if Parameter clear/All parameter clear is executed.
Pr.75 setting
0
Always enabled.
1
When the protective function is activated. Operation continues.
2
Always enabled.
3
When the protective function is activated. Inverter output shutoff
14
Always enabled.
15
When the protective function is activated. Operation continues.
16
Always enabled.
17
When the protective function is activated. Inverter output shutoff
10000
Always enabled.
10001
When the protective function is activated. Operation continues.
10002
Always enabled.
10003
When the protective function is activated. Inverter output shutoff
10014
Always enabled.
10015
When the protective function is activated. Operation continues.
10016
Always enabled.
10017
When the protective function is activated. Inverter output shutoff
 Reset selection (P.E100)
• While P.E100 = "1", or Pr.75 = "1, 3, 15, 17, 10001, 10003, 10015, or 10017", the reset command input is enabled (using
the RES signal or through communication) only when the protective function is activated.
Initial value
Setting range
[E800(-E)]
[E800(-E)]
0 to 3, 14 to 17
14
[E800-SCE]
[E806]
[E800-SCE] [E806]
10014
0 to 3, 14 to 17, 10000 to
10003, 10014 to 10017
0
0
1
0
0
1
0
1
1
[E800(-E)]
[E800(-E)]
0
0
[E800-SCE]
[E800-SCE] [E806]
[E806]
0, 10
10
Operation after PU
Reset input
disconnection is
Operation continues.
Inverter output shutoff
Operation continues.
Inverter output shutoff
Operation continues.
Inverter output shutoff
Operation continues.
Inverter output shutoff
In the initial setting, the reset command input is always
enabled, the inverter operation continues even when PU is
disconnected, the operation can be stopped on the PU, and
the reset limit function is disabled.
In the initial setting, the reset command input is always
enabled, the inverter operation continues even when PU is
disconnected, the operation can be stopped on the PU, and
the reset limit function is enabled.
Reset input is always enabled.
Reset input is enabled only when the protective function is
activated.
Operation continues even when the PU is disconnected.
The inverter output is shut off when the PU is disconnected.
The inverter decelerates to stop when the STOP key on the
PU is pressed in PU operation mode. (The PU stop function is
disabled.)
The inverter decelerates to stop when the STOP key on the
PU is pressed in any operation mode of the PU, external, or
Network. (The PU stop function is enabled.)
Reset limit is fixed to disabled.
Reset limit is initially enabled.
PU stop function
detected
Disabled
Disabled
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
8. (E) Environment Setting Parameters

8.2 Reset selection / disconnected PU detection / PU stop selection

Description
Reset limit
Disabled
Enabled
1
2
3
4
5
6
7
8
9
10
225