Frequently-Used Parameters (Simple Mode Parameters) - Mitsubishi Electric 800 Series Instruction Manual

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

4
BASIC OPERATION
This chapter explains the BASIC OPERATION of this product.
Always read the instructions before using the equipment.
4.1
Frequently-used parameters (simple mode
parameters)
Parameters that are frequently used for the FR-F800 series are grouped as simple mode parameters.
When Pr.160 User group read selection="9999", only the simple mode parameters are displayed.
The simple mode can be used when the operation panel (FR-LU08) or the parameter unit (FR-PU07) is used.
This section explains about frequently-used parameters.
4.1.1
Simple mode parameter list
For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications.
• Pr.160 User group read selection can narrow down the displayed parameters to only the simple mode
parameters. (In the initial setting, all parameters are displayed.) Set Pr.160 User group read selection as
required. (For the parameter change, refer to the Instruction Manual of the FR-LU08.)
Pr.160 setting
9999
0 (initial value)
1
Pr.
Pr.
group
0
G000
Torque boost
1
H400
Maximum frequency
2
H401
Minimum frequency
3
G001
Base frequency
4
D301
Multi-speed setting
(high speed)
5
D302
Multi-speed setting
(middle speed)
6
D303
Multi-speed setting
(low speed)
7
F010
Acceleration time
8
F011
Deceleration time
9
H000
Electronic thermal O/
C103
L relay
15
D200
Jog frequency
16
F002
Jog acceleration/
deceleration time
88
4. BASIC OPERATION

4.1 Frequently-used parameters (simple mode parameters)

Displays only the simple mode parameters.
Displays simple mode + extended parameters.
Displays parameters registered in the user group.
Name
Unit
Initial
value
0.1%
3%
2%
1%
0.01 Hz
120 Hz
60 Hz
0.01 Hz
0Hz
0.01 Hz
60 Hz
0.01 Hz
60 Hz
0.01 Hz
30 Hz
0.01 Hz
10 Hz
0.1 s
5 s
15 s
0.1 s
10 s
30 s
Inverter
*4
0.01 A
rated
*5
current
0.1 A
0.01 Hz
5 Hz
0.1 s
0.5 s
Description
Range
0 to 30%
Set this parameter to obtain a higher starting
*1
torque under V/F control. Also set this when a
*2
loaded motor cannot be driven and the warning
*3
[OL] occurs, then the inverter trips with [OC1].
0 to 120 Hz
Sets the upper limit for the output frequency.
*4
*5
0 to 120 Hz
Sets the lower limit for the output frequency.
0 to 590 Hz
Set this parameter when the rated motor
frequency is 50 Hz.
Check the rating plate of the motor.
0 to 590 Hz
Pre-sets the speeds that will be switched among
by terminals.
0 to 590 Hz
0 to 590 Hz
0 to 3600 s
Sets the acceleration time.
*6
*3
0 to 3600 s
Sets the deceleration time.
*6
*3
Protects the motor from heat.
*4
0 to 500 A
Set the rated motor current.
*5
0 to 3600 A
0 to 590 Hz
Sets the frequency during JOG operation.
0 to 3600 s
Sets motor acceleration/deceleration time
during JOG operation.
Application
Refer to
page
538
253
539
91, 98,
226
190
230
224
224