Output Signal Allocations - YASKAWA SGMJV User Manual

Ac ?-v series
Hide thumbs Also See for SGMJV:
Table of Contents

Advertisement

Display after
Step
Operation
11
12
Turn the power OFF and ON again to enable the change of input signal selections (Pn50A and Pn50B)
<Input signal polarities>
Input signal polarities are as follows when sequence input circuit is connected to a sink circuit. If connected to
a source circuit, polarities are reversed. For details, refer to 3.4.2 Sequence Input Circuit.
Signal
ON
OFF
(4) Checking Input Signals
Input signal status can be checked using the input signal monitor (Un005). As for the input signal monitor
(Un005), refer to 8.4 Monitoring Input Signals.

3.3.2 Output Signal Allocations

Output signals can be allocated to I/O signal connectors (CN1) in accordance with the parameter setting of
Pn50E, Pn50F, Pn510 and Pn512.
(1) Factory Setting
Factory setting can be checked using the following parameters.
Pn50E
Pn50F
Pn510
Keys
MODE/SET
Level
Voltage Level
Low (L) level
0 V
High (H) level
24 V
Allocates /COIN signal to CN1-25, -26.
Allocates /V-CMP signal to CN1-25, -26.
Allocates /TGON signal to CN1-27, -28.
Allocates /S-RDY signal to CN1-29, -30.
Not to use /CLT signal.
Not to use /VLT signal.
Not to use /BK signal.
Not to use /WARN signal.
Not to use /NEAR signal.
Reserved (Cannot be changed)
Reserved (Cannot be changed)
Reserved (Cannot be changed)
Press the DATA/SHIFT Key for approximately one second to
return to the display Pn50B. /S-ON is mapped on CN1-45,
and /P-CL is mapped on CN1-40.
DATA/
Contact
Close
Open
3.3 I/O Signal Allocations
Description
3
3-27