YASKAWA SGMJV User Manual page 382

Ac ?-v series
Hide thumbs Also See for SGMJV:
Table of Contents

Advertisement

11 Appendix
11.2.2 Parameters
Parameter
No.
Input Signal Selection 1
4th
digit
n.
Pn50A
11-22
Name
0000 to FFF1
3rd
2nd
1st
digit
digit
digit
Input Signal Allocation Mode
0
Uses the sequence input signal terminals with standard allocation.
1
Changes the sequence input signal allocation for each signal.
/S-ON Signal Mapping
Signal Polarity: Normal; Servomotor power ON when ON (L-level)
Signal Polarity: Reverse; Servomotor power ON when OFF (H-level)
0
ON when CN1-40 input signal is ON (L-level)
1
ON when CN1-41 input signal is ON (L-level)
2
ON when CN1-42 input signal is ON (L-level)
3
ON when CN1-43 input signal is ON (L-level)
4
ON when CN1-44 input signal is ON (L-level)
5
ON when CN1-45 input signal is ON (L-level)
6
ON when CN1-46 input signal is ON (L-level)
7
Sets signal ON.
8
Sets signal OFF.
9
OFF when CN1-40 input signal is OFF (H-level)
A
OFF when CN1-41 input signal is OFF (H-level)
B
OFF when CN1-42 input signal is OFF (H-level)
C
OFF when CN1-43 input signal is OFF (H-level)
D
OFF when CN1-44 input signal is OFF (H-level)
E
OFF when CN1-45 input signal is OFF (H-level)
F
OFF when CN1-46 input signal is OFF (H-level)
/P-CON Signal Mapping (P control when ON (L-level))
0 to F Same as /S-ON
P-OT Signal Mapping (Overtravel when OFF (H-level))
0
Forward run allowed when CN1-40 input signal is ON (L-level)
1
Forward run allowed when CN1-41 input signal is ON (L-level)
2
Forward run allowed when CN1-42 input signal is ON (L-level)
3
Forward run allowed when CN1-43 input signal is ON (L-level)
4
Forward run allowed when CN1-44 input signal is ON (L-level)
5
Forward run allowed when CN1-45 input signal is ON (L-level)
6
Forward run allowed when CN1-46 input signal is ON (L-level)
7
Forward run prohibited
8
Forward run allowed
9
Forward run allowed when CN1-40 input signal is OFF (H-level)
A
Forward run allowed when CN1-41 input signal is OFF (H-level)
B
Forward run allowed when CN1-42 input signal is OFF (H-level)
C
Forward run allowed when CN1-43 input signal is OFF (H-level)
D
Forward run allowed when CN1-44 input signal is OFF (H-level)
E
Forward run allowed when CN1-45 input signal is OFF (H-level)
F
Forward run allowed when CN1-46 input signal is OFF (H-level)
Setting
Factory
Units
Range
Setting
2100
When
Classification
Enabled
After restart
Setup
(Refer to 3.3.1)
(Refer to 3.3.1.)
(Refer to 5.2.1)
(Refer to 5.2.1.)
(Refer to 6.9.4)
(Refer to 6.8.4.)
(Refer to 5.2.3)
(Refer to 5.2.3.)
Reference
Section

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SgdvSgmavSgmpsSgmgvSgmcs

Table of Contents